Sockets should preferably adopt the two-pole earthed single-phase
sockets that meet the requirements of GB 1002, and also can use
C9/C10 two-pole grounded single-phase sockets (IEC 60320 C13/C14)
that meet the requirements of GB 17465.1; “universal sockets”
should not be used ( Figure).
Figure 2-pole grounded single-phase socket (~250V 10A)
Relevant requirements include:
- The socket reed should have good electrical conductivity and
mechanical elasticity, and has good fatigue resistance, wear
resistance, and corrosion resistance (suggested tin phosphor bronze
material); the minimum force required for pulling a single plug
from the socket should be ≥ 30N, In order to prevent the plug from
falling off automatically during normal use or due to a slight
impact resulting in poor contact.
——The socket should use modular standard parts to facilitate the
assembly and disassembly of the replacement module.
- The rated current of the socket is 10A. In special cases, 16A can
be selected; the jacks are in the order of upper ground (PE), left
zero (N) and right phase.
Temperature rise
When the power distribution unit is connected to the rated current,
the temperature rise of the socket, terminal and fuse connection
shall not exceed 55°C, and the temperature rise of the air switch
and the fuse case shall not exceed 40°C.
Certification
All electrical parts such as terminal blocks, sockets, and
protection devices shall meet the relevant national electrical
safety standards and be of reliable quality; among them, sockets,
terminal blocks, and over-current and short-circuit protection
devices shall pass the national 3C certification.
Grounding, Cables and Other Electrical Accessories
A uniform grounding device (or a grounded copper bar with a
cross-sectional area ≥36 mm2) should be installed in the cabinet.
The cabinet and its internal metal parts shall be connected in a
reliable electrical manner and connected to the grounding device.
Between the grounding copper bar and the grounding of the engine
room is divided into rows (or cabinet top grounding is divided into
rows) between the 16mm2 yellow green and white color single-core
insulated flame-retardant flexible cable reliable connection.
All cables in the cabinet should meet the requirements of YD/T
1173. The color of the insulating layer or outer sheath of cables
and busbars shall meet the requirements of GB7947.
If you have an audible alarm function, you must have the function
of manually turning off the alarm sound. After the current value
returns to normal, the alarm should be automatically restored. The
alarm threshold should be set as required. In addition, the cabinet
can provide power off alarms. The current indication and alarm
indication should be installed above the rear of the rack. Should
not be installed on the door. When the cabinet needs to use light
indications, LED indicators should be used.
Electrical Protection Performance
The insulation resistance of each live circuit in the cabinet (the
circuit is not directly grounded) to the ground (or cabinet) should
be ≥10MΩ (after reading for 1 min at 500V megohmmeter).
Each live circuit in the cabinet (or cabinet) and two
non-electrically connected live circuits shall be able to withstand
a sinusoidal test voltage of 2500V and 50Hz for 1min without any
breakdown or arcing. The leakage current is ≤10mA.
Each cabinet requires the installation of a box type empty open
box. The standard configuration has 8 open circuits, and the open
MAX load current ampere is proposed by the engineering design. Four
power supply outlets. A shielding plate is installed in front of
the power distribution box to avoid accidentally closing the
air-opening.
The air-opening brand is: In order to ensure the safety of
equipment power, it is forbidden to open it with a small factory.
It is recommended to use GE, Schneider, ABB, and Merlin products.
Each rack is equipped with standard length 500mm, width 50mm, and
rear 5mm high-quality copper plate as worksites and protective
grounds. Each row is tapped with 20 holes and equipped with 20 sets
of bolts.
The chassis of the cabinet should be strictly grounded to prevent
electric leakage. The grounding of the plates, cabinets, tables and
boxes should be solid and good. Openable doors with electrical
appliances should be reliably connected with bare copper cords and
grounded metal structures. All grounding devices shall be securely
fastened and spring washers or lock nuts shall be provided to
prevent loosening. If the cabinet has a shielded ground, or other
electronic components grounded. The grounding strips used must be
insulated from the main grounding strips and connected to the main
grounding strips when connected to the main grounding strips
![]() |